DC Signal Control Line Lightning Protector
Contact Info
- Add:深圳市龙华区大浪街道龙华社区龙军花园9栋2单元1202, Zip: 518023
- Contact: 刘先生
- Tel:0755-88834928
- Email:1002196429@qq.com
Other Products
| Performance Overview FRD, FLD Protectors | Usage Advantages |
| Mounted on 35mm DIN rail | Can be directly installed in distribution cabinets or switch boxes |
| Capable of providing various voltages without issues | Enables user-oriented surge protection |
| Screwless compression terminals | Easy installation |
| Y-circuit design | Safe and reliable, effectively suppresses surges from phase, neutral, or protective earth lines |
Function and Application Areas
TKS-B, FRD, FLD, FRD2, and FLD2 are protectors used for electronic measurement and control lines, preventing damage to associated equipment from surge overvoltages caused by lightning or traveling waves on data lines.
TKS-B is a protector applied to all data lines with voltages not exceeding 110V and frequencies not exceeding 2MHz, installed in LPZ 0→2.
The FRD and FLD series protectors are used in ungrounded (asymmetric, floating) two-wire systems. FRD can be installed in circuits where resistance increase is permissible; if resistance increase is not allowed, FLD is used.
The FRD2 and FLD2 series protectors are specifically designed for earth-referenced single-wire systems (symmetric, voltage-dependent). Here, there is also a choice between series resistance and series inductance: FRD2 is selected if resistance increase is permissible, while FLD2 is chosen for voltage-controlled devices. Due to their two-stage protection circuit design, they are also suitable for installation in LPZ1→LPZ3.
The two-stage circuit of FRD and FLD consists of gas discharge tubes, varistors, and clamping diodes, featuring high flow capacity, extremely short clamping time, and low protection level.
The TKS-B protector has only a single-stage protection circuit but offers exceptionally high flow capacity.
Installation
OBO TKS-B, FRD, and FLD type protectors can be installed in any standard switch box or distribution box, simply mounted on a 35mm DIN rail. Screwless terminals reduce installation costs.
Technical Parameters
| Surge Arrester | FRD-5 | FRD-12 | FRD-24 | FRD-48 | FRD-60 | FRD-110 | TKS-B |
| LPZ | 1→3 | 0→2 | |||||
| Rated Voltage UN Max. Continuous Operating Voltage UC | 5V 6V | 12V 13.5V | 24V 27V | 48V 53V | 60V 66V | 110V 122V | 110V 130V |
| Rated Load Current FRD, FRD2 IL | 0.2A | 16A | |||||
| Rated Load Current FLD, FLD2 | 1.0A | ||||||
| Nominal Discharge Current (8/20) In | 10kA | 20kA | |||||
| Impulse Current Capacity (10/350) Iimp | 6kA | ||||||
| Voltage Protection Level Up3-4 | ≤13V | ≤29V | ≤51V | ≤100V | ≤130V | ≤300V | ≤450V |
| Series Resistance per Line FRD, FRD2 R | 15Ω | ||||||
| Series Inductance per Line FLD, FLD2 L | 100 μH | ||||||
| Connection Wire Cross-Section Connection Wire Strip Length Color Material Installation Dimensions | 0.14-2.5mm² 6-7mm Light gray, similar to RAL 7035 Polyamide 6 Mounted on 35mm DIN rail according to DIN EN 50022 Length 90mm, width 17.8mm, depth 62mm | ||||||
| Industry Category | Electrical-Equipment-Supplies |
|---|---|
| Product Category | |
| Brand: | 德国obo |
| Spec: | FRD, FLD, TKS-B |
| Stock: | |
| Origin: | China / Guangdong / Shenshi |